#18552 F102 Medium

F102+8026

Oliver Marshall Open
Problem: F102+8026 estop installed on the slab below the mezzanine.
Solution: Relocate onto the mezzanine walkway as per the SAL and 3D. The cable is long enough for this change. Inform commissioning when this is completed. See files for SAL, 3D etc. Then remove any unused containment and floor bolts.
Assignee: Calum Greenwell
Causing: TGW Limited
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18553 F122 Medium

F122+8026

Oliver Marshall Open
Problem: F122+8026 estop installed on the slab below the mezzanine.
Solution: Relocate onto the mezzanine walkway as per the SAL and 3D. The cable is long enough for this change. Inform commissioning when this is completed. See files for SAL, 3D etc. Then remove any unused containment and floor bolts.  
Assignee: Calum Greenwell
Causing: TGW Limited
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18551 F125 Low

ASI Module Ident Labels

Alexander Marks Open
Problem: ASI Module missing ident label on module itself and cable ident tag
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18537 F221 Medium

Noisy motor

Nick Barnes Closed
Problem: Noise coming from motor. Check wiring
Solution: Check wiring - set up. Noise originally thought to be loose roller from ground level.
Assignee: Oliver Marshall
Causing:
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18554 F521 Medium

F521+1223 damaged brake logic box enclosure

Oliver Marshall Open
Problem: This looks like the box has been damaged by a lifter. We don't know who did this damage.
Solution: Depending on parts replace the whole BLB or parts from non working BLBs.
Assignee: Calum Greenwell
Causing: TGW Limited
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18483 F901 Low

Control Button Gland

Alexander Marks Work Completed
Problem: Kopex gland on control button is loose needs tightening F901+8209-U3000 F901+8521-U3000 F901+8533-U3000 F901+8530-U3000
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18484 F901 Low

PSU102 Panel

Alexander Marks Work Completed
Problem: Profinet cable ident labels inside panel need to be secured with cable tie at both ends F901+PSU102
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18485 F901 Low

Control Button Cable Ident Label

Alexander Marks Work Completed
Problem: Ident label not attached to Kopex fully  F901+8032-U3001
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18487 F901 Low

Maintenance Switch Cable Ident Label

Alexander Marks Open
Problem: Maintenance switch cable ident label not attached to kopex
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18488 F901 Low

Ident Label Control Cable

Alexander Marks Open
Problem: Ident label is incorrect. Cable for stop front sensor is tagged up as 3W4035, this is for a proximity sensor, should be 3W4033
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18489 F901 Low

Cable dressing

Alexander Marks Open
Problem: Where possible excess cable should be dressed and lost in basket rather than coiled  F901+1258-U4001 F901+1273-U4001 F901.1136
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18491 F901 Low

Profinet Cable

Alexander Marks Open
Problem: Profinet cable at motors not has been disconnected  F901.1178
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18493 F901 Low

ASI Cable

Alexander Marks Open
Problem: ASI cable terminated into ASI module needs to be cut flush with the module F901+1268.012-X3111
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18495 F901 Low

Brake Logic Box

Alexander Marks Open
Problem: Unused brake cable needs disconnecting  F901+1337.021-U3113
Assignee: Ian Thomas
Causing:
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18507 F901 Low

Main incoming Cable

Steven Dawson Open
Problem: Missing cable ident. F901.11
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18508 F901 Low

Profinet cables

Steven Dawson Open
Problem: Labels not fitted correctly. F901.PSU11 
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18509 F901 Low

Profinet cables

Steven Dawson Open
Problem: Cable are labled wrong. Idents should be at the RJ45  F901.EMS11
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18511 F901 Low

Control buttons

Steven Dawson Open
Problem: Kopex glands loose F901.8011 & 8021
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18512 F901 Medium

Main incoming cable

Steven Dawson Open
Problem: Excessive sheath on cable and needs dressing correctly  F901.SS13
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18513 F901 Low

Profinet Cables

Steven Dawson Open
Problem: Cable idents not fitted correctly. F901.PSU12
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18514 F901 Medium

Main incoming cables

Steven Dawson Open
Problem: Dress and re terminate cables F901.PSU12 
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18520 F901 Low

Beacon Kopex

Alexander Marks Open
Problem: Beacon Kopex not secured to conveyor side profile, cable inside sheath also appears damaged  F901+7017-3W3101 F901+7018-3W3101
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18547 F901 Low

M12 Splitter

Alexander Marks Open
Problem: M12 Splitter is bent  F901+1139-A4011
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18548 F901 Low

Control Button Damaged

Alexander Marks Open
Problem: Control button casing damaged on outside  F901+8512-U3000
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18549 F901 Low

Control Cable

Alexander Marks Open
Problem: Control Cable at inverter has connector removed, looks like it needs to be removed.  F901+1244-A4011
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18540 F901 Low

Control Cable Ident Label

Alexander Marks Open
Problem: Control cable from maintenance switch to inverter is missing ident label at inverter end. Cable ID missing F901+1153-3W4003 F901+1154-A4011
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18526 F903 Medium

Cable routing

Luke McAuley Open
Problem: Profi Cable to be correctly routed in the basket 
Assignee: Oliver Marshall
Causing:
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18492 Critical

Kupplungssatz Jumperkabel

Reinhold Siegl Work In Progress
Problem: Kupplungssatz Jumperkabel nicht mehr auffindbar
Solution: 20 x KupSatz_JumpKab_mZusHa nachsenden    
Assignee: Reinhold Siegl
Causing:
Conf: medium
Created: 2026-06-29T00:00:00+00:00

CTC × Mechanical

CTC×Mechanical

7
#18522 F121 High

Damaged belt

Nick Barnes Open
Problem: Damaged belt
Solution: RCA and and fit new.
Assignee: Joel Standfest
Causing:
Conf: high
Created: 2026-06-29T00:00:00+00:00
#18490 F321_E2S South 1.A031 Medium

Damaged belt

Lewis Campkin Work In Progress
Problem: Damaged belt
Solution: Can we order a replacement please
Assignee: Reinhold Siegl
Causing:
Conf: high
Created: 2026-06-29T00:00:00+00:00
#18498 F521 Medium

Chris Campkin Open
Problem: Wrong covers
Assignee: Chris Campkin
Causing:
Conf: high
Created: 2026-06-29T00:00:00+00:00
#18536 F822 Medium

Rubin

Luke McAuley Open
Problem: Missing Rubilin strip
Assignee: Chris Campkin
Causing:
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18486 F901 Low

M12 Cap Cover

Alexander Marks Open
Problem: M12 Cap cover missing off unused connection  multiple  F901+1169-A4011 F901+1258-M4001.A1 F901+1259-A4011 F901+1229-A4011 F901+1154-A4011 F901+1244-A4011
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18497 F901 Low

Proximity Sensor Cable

Alexander Marks Open
Problem: Proximity sensor on belt conveyor near sorter not connected multiple points check whole line  F901+1243-3W4034 F901+1244-3W4035 (under rollers) F901+1153-3W4034
Assignee: Oliver Marshall
Causing:
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18519 F901 Low

Motor

Steven Dawson Open
Problem: Missing dust cap F901.1123
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00

STW × Mechanical

STW×Mechanical

15
#18542 Dematic Sorter Medium

TGU - Additional

Gabriel Pintea Open
Problem: Installed safety netting along the mezzanine handrails on the south sorter to prevent objects from falling from the sorter onto the area below. The work was completed in accordance with site safety requirements, ensuring the netting was securely fixed and provided continuous protection along the designated mezzanine sections.
Solution: Installed safety netting along the mezzanine handrails on the south sorter to prevent objects from falling from the sorter onto the area below. The work was completed in accordance with site safety requirements, ensuring the netting was securely fixed and provided continuous protection along the designated mezzanine sections.
Assignee: Tomasz Urbanski
Causing:
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18496 F105, 125 Medium

Facia waste line

Chris Campkin Open
Problem: Not enough facia please order 30-40 lengths TASK FORCE
Assignee: Florian Hewald (on vacation)
Causing:
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18550 F125 Low

Basket Lid

Alexander Marks Open
Problem: Edge protection missing off basket lid  F125.1117 F125.1116
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18543 F125/F105 Medium

TGU - Additional

Gabriel Pintea Open
Problem: IPAF Operator & MEWP Support for TGW (29/06)
Solution: Provided an IPAF operator and MEWP to support TGW operations on 29/06 for a total of 6 hours.
Assignee: Tomasz Urbanski
Causing:
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18503 F901 Low

Basket lid

Steven Dawson Open
Problem: Basket lid not fitted  F901.1317
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18505 F901 Low

Basket Lid

Steven Dawson Open
Problem: Lid missing edge protection. F901.ES11
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18515 F901 Low

Basket Lid

Steven Dawson Open
Problem: Sharp points on lid cuts F901.1309
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18516 F901 Low

Basket Lid

Steven Dawson Open
Problem: Basket lid not sitting right on basket  F901.1294
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18518 F901 Low

Basket lid

Steven Dawson Open
Problem: Gap in basket lid F901.1281
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18521 F901 Low

Basket Lid

Alexander Marks Open
Problem: Basket lid not sitting on basket correctly  F901+1136
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18545 F901 Low

Basket Lid

Alexander Marks Open
Problem: Basket Lid overhanging basket on mez F901.1133
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18546 F901 Medium

Sharp Edges

Alexander Marks Open
Problem: Basket Lid corners are sharp need filing down  F901+1133
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18529 F903 Medium

Missing finger trap guards

Luke McAuley Open
Problem: Missing finger trap guards between rods 
Assignee: Chris Campkin
Causing:
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18541 F903 Medium

Missing fascia

Luke McAuley Open
Problem: Missing fascia 
Assignee: Tomasz Kujawa
Causing: TGU Eng Limited
Conf: medium
Created: 2026-06-30T00:00:00+00:00
#18544 Spirals Medium

TGU - Additional

Gabriel Pintea Open
Problem: IPAF Operator & MEWP Support for Amberflex via TGW (29/06)
Solution: Provided an additional IPAF operator and MEWP on 29/06 at the request of TGW to support Amberflex for 4 hours.
Assignee: Tomasz Urbanski
Causing:
Conf: high
Created: 2026-06-30T00:00:00+00:00

COMM × Commissioning

COMM×Commissioning

9
#18530 F902 Medium

Vendor IP

Dan Radu Open
Problem: no vendor IP added to the folder structure. still under commissioning
Assignee: Nathan Bruce
Causing:
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18531 F902 Medium

Lib Update

Dan Radu Open
Problem: Lib not updated to the latest version . still under comms
Assignee: Nathan Bruce
Causing:
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18532 F902 Medium

Jam Reset button- inop

Dan Radu Open
Problem: 8505 Jam reset station INOP
Assignee: Nathan Bruce
Causing:
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18533 F902 Medium

8514 Jam Station

Dan Radu Work Completed
Problem: 8514 Jam reset inop
Solution: poor connection inside NO contact
Assignee: Nathan Bruce
Causing:
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18534 F902 Medium

8511 Jam Station -inop

Dan Radu Work Completed
Problem: 8511 reset push button , INOP
Solution: loose connection inside NO contact
Assignee: Nathan Bruce
Causing:
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18535 F902 Medium

8508 reset station

Dan Radu Work Completed
Problem: reset push button inop
Solution: loose connection inside NO contact
Assignee: Nathan Bruce
Causing:
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18538 F902 Medium

Jam Reset 8527 incorrect colour LED

David Moore Closed
Problem: Jam Reset button 8527 incorrect colour LED- Green fitted-=should be white
Solution: Completed.
Assignee: Calum Greenwell
Causing:
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18539 F902 Medium

FC_SafLac - LAC20 feedbacks incorrect

David Moore Work Completed
Problem: FC_SafLac - LAC20 feedbacks incorrect - Should be Mc10
Solution: SW changed by CommC
Assignee: Nathan Bruce
Causing:
Conf: high
Created: 2026-06-30T00:00:00+00:00
#18494 Fxxx Medium

Red Pen PID Station

Florian Schöner Closed
Problem: Unluckily there was a Red Pen correction. Can you please adapt it
Solution: eplan has been updated
Assignee: Peter Köstlinger
Causing:
Conf: high
Created: 2026-06-29T00:00:00+00:00

COMM × Electrical

COMM×Electrical

4
#18517 F901 Low

Maintenance Switch

Steven Dawson Open
Problem: Loose auxiliary socket  F901.1283
Assignee: Jason Brettle
Causing: Hills Electrical Contractors Ltd.
Conf: high
Created: 2026-06-29T00:00:00+00:00
#18482 F903 Medium

Damaged reflector

Jamie Mcauley Work Completed
Problem: Damaged reflector
Assignee: Chris Campkin
Causing:
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18527 F903 Medium

Damaged roller bands

Luke McAuley Open
Problem: Damaged roller bands 
Assignee: Chris Campkin
Causing:
Conf: medium
Created: 2026-06-29T00:00:00+00:00
#18528 F903 Medium

Jumper cables

Luke McAuley Work Completed
Problem: Jumper cables not tied or clipped up 
Assignee: Chris Campkin
Causing:
Conf: high
Created: 2026-06-29T00:00:00+00:00